Model | RTPV-1085 |
Rated Current | 10/15/20/25/30A |
Max Current | 30A |
Rated Voltage Ue | DC1500V |
Rated Breaking Capacity (Ics) | 50kA |
Breaking capacity and applicable category gPV | "GPV" refers to a fuse used in photovoltaic power systems with full range DC breaking capacity. |
Altitude | ≤3500m |
Protection Class | IP20 |
Pollution Degree | Level 3 |
Installation Category | Class I, The fuse is installed in a place without significant shaking and impact vibration |
Ambient Temperature | -25°C ~ +60°C |
Maximum relative humidity | Not exceeding 90% |
Installation | 35MM DIN Rail |
Applicable Wire Specifications | 0.8mm ²-6mm ², Temperature resistance of 75 °C/90 °C |
Tightening Torque | 2.3N.m |
Terminal Connection Type | Phillips Screws |
International Standard | GB/T 13539.6-2013,IEC 60269-6:2010 |